What does non-combustibility mean for a mineral wool wall panel?

At a glance

Mineral wool and a finished sandwich panel have separate fire classifications. The panel also contains facings, coatings and adhesive. Check both the reaction to fire of the complete panel and the fire resistance of the assembled wall. This distinction matters when doors or services are added years later. A1 is the highest reaction-to-fire class. Many finished mineral wool panels have a declared class of A2-s1,d0, which takes the complete product into account. Specify the documented class of the panel with its adhesive and coated steel facings. An A1 rating for the insulation alone applies only to that material.

Enclosed plant room made from sandwich panels inside a factory

Identify the product covered by A1 or A2

Look up the exact product in its documentation. Check that panel thickness, facings and other conditions fall within the classification. A change in coating material or panel construction may require separate evidence. A general statement about mineral wool cannot identify the performance of a particular panel.

Read the smoke and droplet classifications

The s1 designation indicates limited smoke production under the relevant test conditions. Smoke can still develop in a building fire. The d0 designation means that no flaming droplets or particles occurred within the classification criteria. It describes behaviour under those conditions only.

Reaction to fire describes how a product contributes to fire development. The length of time a wall can separate two rooms requires a different assessment. An A2-s1,d0 classification alone provides no basis for specifying EI 60 or EI 120.

Check the wall assembly covered by the EI rating

E stands for integrity and I for insulation in a fire. The number gives the time in minutes for which the relevant classification criteria were met. R applies where loadbearing capacity in fire is assessed. Use it only for an element classified for that function.

Check the complete field of application, including panel type, thickness, span, vertical or horizontal installation, fixings and direction of fire exposure. A rating obtained for one arrangement may cover only certain lengths and joints. Keep the design within the documented limits.

Match the documents to the installed product

Datasheets of different dates may cover variants with similar names. Before specifying a value, match the product and its configuration to the document. Keep the version used for the order with the evidence supporting the design. A later catalogue change need not alter the properties of an earlier delivery. For an extension, establish how the existing and new sections of wall will work together.

Mineral wool sandwich panels – free quote from SteelProfil

Assess the effect of new openings

Doors, grilles and service penetrations each need an appropriate detail. A gap around a pipe still needs assessment when mineral wool surrounds it. Select the seal for the wall, the service and the required performance. Ordinary expanding foam cannot simply replace a specified penetration seal.

Before cutting an opening, establish whether the wall has a fire separation function. Keep a record of alterations while the building is in use. Uncoordinated changes can compromise the performance assumed in the design even when the original panel was correctly specified.

Select a compatible replacement panel

Replacing a damaged panel means restoring the specified assembly. In addition to colour and thickness, check joint geometry, seals, number of fixings and connections to adjoining elements. Identify clearance stock and assess its condition before use.

Following heat exposure or a fire, inspect the bond between the layers, deformation and connections. The appearance of the steel alone cannot establish serviceability. Repainting may improve the finish but provides no evidence of structural performance or fire resistance.

Keep the fire documentation with the building records

Retain the declaration of performance, details of the installed system and as-built records. When a tenant changes, information about the function of each wall matters as much as the services drawings. It shows which alterations require agreement before work starts.

During inspections, check penetration seals, closures at openings and damage to the cladding. Maintaining fire protection throughout the building’s life means keeping the entire wall within its classified configuration, including after repairs and extensions.

Questions and answers

Does every mineral wool panel have an A1 classification?

No. The core and the finished panel have separate classifications. Many steel-faced mineral wool panels are declared A2-s1,d0. Check the documentation for the exact configuration.

Does A2-s1,d0 specify a fire resistance period in minutes?

No. A2-s1,d0 describes reaction to fire. A separate wall classification, such as EI, gives the time for the relevant criteria and defines the configurations covered.

7 branches. Materials closer to your project.

Map of seven branches offering sandwich panels, PIR boards and sheet metal — Ecoprofil
  • SEROCK — Dzierżenin 34 E [map]
  • BŁONIE — ul. Sochaczewska 138A [map]
  • RADOM — ul. Grobickiego 8 [map]
  • ŁÓDŹ — Natolin 8 [map]
  • OLSZTYN — Barczewo, ul. Prosta 9 [map]
  • WROCŁAW — ul. Jerzmanowska 10C [map]
  • GORZÓW WLKP. — ul. Zielona 33/34 [map]

Check prices and availability: +48 500 409 109

Free quote

Materials for your project

You may also find useful…